High requirements for the vacuum degree of the unit. The crew needs to perform daily maintenance on a regular basis. The main content of the Cold King agent is as follows:

1. When the short-term shutdown time is within 1-2 weeks, the main maintenance work is to maintain the vacuum degree of the unit. Monitor the vacuum level twice a day in the morning and twice in the evening. For accuracy, start and run the generator pump and absorber pump for 10 minutes before observing the pressure gauge, then observe the reading on the pressure gauge and compare it with the previous one.
2. When the machine is shut down for long-term maintenance, all the chilled water in the evaporator should be bypassed to the absorption tower, and the solution should be evenly diluted to prevent crystallization at ambient temperature. There is no unified regulation on maintenance methods during shutdown.
Generally, vacuum nitrogen filling maintenance method is used. Nitrogen filling maintenance is to fill the unit with about 49kPa (gauge pressure) of nitrogen gas after confirming that there is no leakage, so that it is always in a positive pressure state. This ensures that the refrigeration unit will not leak into the air in case of leakage and can be detected at any time, which is very convenient. Its disadvantage is that due to the complex structure and process of the device, it is difficult to achieve denitrification in one go.
Vacuum maintenance refers to maintaining high vacuum after the unit is shut down. This method is relatively simple, saving both costs and nitrogen filling process operations. If the vacuum degree of the refrigeration machine is still qualified before trial operation, it can be directly started and put into operation.
Vacuum maintenance also has drawbacks: if the monitoring is not strict or the analysis error rate is incorrect, it will leak into the air and cause corrosion. In addition, if the refrigerator leaks due to poor sealing quality, nitrogen gas should be filled and pressurized for leak detection.
Therefore, it is better to charge nitrogen immediately after parking than after a leak. Of course, for a refrigerator with good sealing quality, this is another matter. Assign a dedicated person to monitor the vacuum level of the unit twice a day and perform vacuum maintenance. If there is a leak, it should be dealt with immediately without delay.
3. The internal cleaning of the refrigerator is a chemical cleaning of the refrigerant circulation system. When the interior of the refrigerator is severely corroded and unable to function properly, cleaning the refrigerator cavity is a method. Usually cleaned every 4-5 years.
By cleaning, all rust caused by corrosion in the internal cavity of the unit can be completely removed, improving the heat transfer effect of the internal cavity, enhancing the spraying effect, ensuring the normal operation of the shielded pump, and preventing impurities from affecting the newly filled liquid, fully exerting the cooling power under normal conditions.
The pre film agent acts on the surface of the material through the pre film on the inner wall of the device, producing an inert protective film, thereby reducing the corrosion of the device and extending its service life.